Cable Size Chart

Cable Sizes for Submersible Motors

Use this chart to pick the cable size for your submersible pump motor. Find your motor size, then read across to find the longest cable run for each cable size. If your run is longer than the figure shown, go up a cable size or talk to an engineer.

Single Phase 230V-50Hz

Cable section in mm² — maximum cable length in metres.

kWHP4 x 14 x 1.54 x 2.54 x 44 x 64 x 104 x 16
0.370.506090140    
0.550.754570110180   
0.751355085140210  
1.11.525356095145240 
1.52 304575115190305
2.23  305075125200

Three Phase 230V-50Hz

Cable section in mm² — maximum cable length in metres.

kWHP4 x 14 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 70
0.370.50100152255        
0.550.7583126210338       
0.7516599165265405      
1.11.54872120192292485     
1.52 5388142215360     
2.23  6097147245392    
34  4773110183295510   
45.5   5583138220380   
5.57.5    60100160275385  
7.510    4573114195275395 
9.212.5     64100157220315 
1115     5487135190270378
1317.5      75117164236330
1520      65102144205287
18.525       82114162225
2230       6995137190
3040        70102142

Three Phase 400V-50Hz

Cable section in mm² — maximum cable length in metres.

kWHP4 x 14 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 70
0.370.50300          
0.550.75250380         
0.751195295         
1.11.5145215360        
1.52105160265425       
2.2370110180290440      
345585140220330      
45.54060105165250415     
5.57.5 4575120180300480    
7.510 355595135220340585   
9.212.5  4775115190300470   
1115  406595160260405   
1317.5   6085140225350490  
1520   5075125195305430  
18.525    58100155245340485 
2230    4985130205285410570
3040    366396152210305425

Voltage drop 3% — Maximum environment temperature + 30 °C.